== Time control ==
The goal of the '''time control''' is to maintain the long-term frequency at the specified value within a [[wide area synchronous grid]]. Due to the disturbances, the average frequency drifts, and a ''time error'' accumulates between the official time and the time measured in the AC cycles. In the US, the average 60 Hz frequency is maintained within each [[Wide area synchronous grid|interconnection]] by a designated entity, '''time monitor''', that periodically forces a grid frequency change to bring the overall time offset within the predefined limits. For example, in the [[Eastern Interconnection]] the action (temporarily setting the frequency to 60.02 Hz or 59.98 Hz) is initiated when the time offset reaches 10 seconds and ceases once the offset reaches 6 seconds. Time control is performed either by a computer (''Automatic Time Error Correction''), or by the monitor requesting balancing authorities to adjust their settings.{{sfn|NERC|2011|pp=13-14}}
 